507 research outputs found

    Distributed Generation as Voltage Support for Single Wire Earth Return Systems

    Get PDF
    Key issues for distributed generation (DG) inclusion in a distribution system include operation, control, protection, harmonics, and transients. This paper analyzes two of the main issues: operation and control for DG installation. Inclusion of DG in distribution networks has the potential to adversely affect the control of voltage. Both DG and tap changers aim to improve voltage profile of the network, and hence they can interact causing unstable operation or increased losses. Simulations show that a fast responding DG with appropriate voltage references is capable of reduction of such problems in the network. A DG control model is developed based on voltage sensitivity of lines and evaluated on a single wire earth return (SWER) system. An investigation of voltage interaction between DG controllers is conducted and interaction-index is developed to predict the degree of interaction. From the simulation it is found that the best power factor for DG injection to achieve voltage correction becomes higher for high resistance lines. A drastic reduction in power losses can be achieved in SWER systems if DG is installed. Multiple DG can aid voltage profile of feeder and should provide higher reliability. Setting the voltage references of separate DGs can provide a graduated response to voltage correction

    Compensation of Distribution System Voltage using DVR

    Get PDF
    A dynamic voltage restorer (DVR) is a power-electronic controller that can protect sensitive loads from disturbances in the supply system. In this paper, it is demonstrated that this device can tightly regulate the voltage at the load terminal against imbalance or harmonic in the source side. The behavior of the device is studied through steady-state analysis, and limits to achievable performance are found. This analysis is extended to the study of transient operation where the generation of the reference voltage of the DVR is discussed. Once the reference signals are generated, they are tracked using a switching band scheme. A suitable structure in which the DVR is realized by voltage-source inverters (VSIs) is also discussed. Particular emphasis to the rating of this device is provided. Extensive simulation results are included to illustrate the operating principles of a DVR

    Decomposition of aggregated load: finding induction motor fraction in real load

    Get PDF
    The main contribution of this paper is decomposition/separation of the compositie induction motors load from measurement at a system bus. In power system transmission buses load is represented by static and dynamic loads. The induction motor is considered as the main dynamic loads and in the practice for major transmission buses there will be many and various induction motors contributing. Particularly at an industrial bus most of the load is dynamic types. Rather than traing to extract models of many machines this paper seeks to identify three groups of induction motors to represent the dynamic loads. Three groups of induction motors used to characterize the load. These are the small groups (4kw to 11kw), the medium groups (15kw to 180kw) and the large groups (above 630kw). At first these groups with different percentage contribution of each group is composite. After that from the composite models, each motor percentage contribution is decomposed by using the least square algorithms. In power system commercial and the residential buses static loads percentage is higher than the dynamic loads percentage. To apply this theory to other types of buses such as residential and commerical it is good practice to represent the total load as a combination of composite motor loads, constant impedence loads and constant power loads. To validate the theory, the 24hrs of Sydney West data is decomposed according to the three groups of motor models

    SRAT-Distribution Voltage Sags and Reliability Assessment Tool

    Get PDF
    Interruptions to supply and sags of distribution system voltage are the main aspects causing customer complaints. There is a need for analysis of supply reliability and voltage sag to relate system performance with network structure and equipment design parameters. This analysis can also give prediction of voltage dips, as well as relating traditional reliability and momentary outage measures to the properties of protection systems and to network impedances. Existing reliability analysis software often requires substantial training, lacks automated facilities, and suffers from data availability. Thus it requires time-consuming manual intervention for the study of large networks. A user-friendly sag and reliability assessment tool (SRAT) has been developed based on existing impedance data, protection characteristics, and a model of failure probability. The new features included in SRAT are a) efficient reliability and sag assessments for a radial network with limited loops, b) reliability evaluation associated with realistic protection and restoration schemes, c) inclusion of momentary outages in the same model as permanent outage evaluation, d) evaluation of the sag transfer through meshed subtransmission network, and e) simplified probability distribution model determined from available faults records. Examples of the application of the tools to an Australian distribution network are used to illustrate the application of this model

    A database ATP simulated waveforms of shunt reactor switching cases with vacuum breakers on motor circuits

    Get PDF
    This paper presents a database ATP (Alternative Transient Program) simulated waveforms for shunt reactor switching cases with vacuum breakers in motor circuits following interruption of the starting current. The targeted objective is to provide multiple reignition simulated data for diagnostic and prognostic algorithms development, but also to help ATP users with practical study cases and component data compilation for shunt reactor switching. This method can be easily applied with different data for the different dielectric curves of circuit-breakers and networks. This paper presents design details, discusses some of the available cases and the advantages of such simulated data

    Development of diagnostic and prognostic algorithms for SF6 puffer circuit breakers from transient waveforms: a validation proposal

    Get PDF
    - This paper presents a validation proposal for development of diagnostic and prognostic algorithms for SF6 puffer circuit-breakers reproduced from actual site waveforms. The re-ignition/restriking rates are duplicated in given circuits and the cumulative energy dissipated in interrupters by the restriking currents. The targeted objective is to provide a simulated database for diagnosis of re-ignition/restrikes relating to the phase to earth voltage and the number of re-ignition/restrikes as well as estimating the remaining life of SF6 circuit-breakers. The model-based diagnosis of a tool will be useful in monitoring re-ignition/restrikes as well as predicting a nozzle’s lifetime. This will help ATP users with practical study cases and component data compilation for shunt reactor switching and capacitor switching. This method can be easily applied with different data for the different dielectric curves of circuit breakers and networks. This paper presents modelling details and some of the available cases, required project support, the validation proposal, the specific plan for implementation and the propsed main contributions

    Distributed Market Clearing Approach for Local Energy Trading in Transactive Market

    Full text link
    This paper proposes a market clearing mechanism for energy trading in a local transactive market, where each player can participate in the market as seller or buyer and tries to maximize its welfare individually. Market players send their demand and supply to a local data center, where clearing price is determined to balance demand and supply. The topology of the grid and associated network constraints are considered to compute a price signal in the data center to keep the system secure by applying this signal to the corresponding players. The proposed approach needs only the demanded/supplied power by each player to reach global optimum which means that utility and cost function parameters would remain private. Also, this approach uses distributed method by applying local market clearing price as coordination information and direct load flow (DLF) for power flow calculation saving computation resources and making it suitable for online and automatic operation for a market with a large number of players. The proposed method is tested on a market with 50 players and simulation results show that the convergence is guaranteed and the proposed distributed method can reach the same result as conventional centralized approach.Comment: Accepted paper. To appear in PESGM 2018, Portland, OR, 201

    Line protection in inverter supplied networks

    Get PDF
    New protection methods are required to protect a distribution system when supplied by current limited converters. In this paper, a method of converter control is proposed to limit the current by reducing the voltage in the faulted phase or phases while keeping the voltage of the healthy phases unaltered. Unsymmetrical fault analysis is performed to calculate the sequence currents and voltages at the relay location, when system is supplied by a converter. Based on that converter control, distance relay performances have been evaluated in both grid-connected and islanded mode operations. Distance relay, combined with MHO and negative sequence impedance directional characteristics, is proposed as a protection scheme for the distribution system for different types of faults under the current limited environment. The results are validated through PSCAD/EMTDC simulation and MATLAB calculations

    Distributed Generation Control using Protection Principles

    Get PDF
    In a distribution system, it is essential to maintain the voltage variation within a specified limit for satisfactory operation of connected customers' equipment. Normally, this goal is achieved by controlling the operation of compensating devices, such as load tap changing transformers, shunt capacitors, series capacitors, shunt reactors, and static VAr compensators. However, technical and regulatory developments are encouraging a greater number of small generator units, known as Distributed Generation (DG), and this has the potential to significantly affect voltage control systems. This paper presents an adaptive voltage control technique which incorporates DG systems into the voltage control system. The control scheme uses On-load Tap Changing Transformer (OLTC) and DG for voltage corrections, both are driven by advanced Line Drop Compensators (LDC). At the substation, the LDC is employed to control step up or step down decisions of the OLTC, while another LDC will be used at DG connection point to set DG parameters. Also, for a more cost-effective system, voltage control action coordination is proposed using magnitude grading and time grading. The control approach is tested on a modified distribution system with load variations that are stochastic in time and location. The results show that the integration of these magnitude grading and time grading, protection principles have considerably reduced the DG energy required to achieve the desired control

    Enhancing the stability of an autonomous microgrid using DSTATCOM

    Get PDF
    This paper proposes a method for power sharing in autonomous microgrid with multiple distributed generators (DG). It is assumed that all the DGs are connected through voltage source converter (VSC) and all connected loads are passive, making the microgrid totally inertia less. The VSCs are controlled by either state feedback or current feedback mode to achieve desired voltage-current or power outputs respectively. A modified angle droop is used for DG voltage reference generation. Power sharing ratio of the proposed droop control is established through deriva-tion and verified by simulation results. A distribution static compensator (DSTATCOM) is connected in the microgrid to provide ride through capability during power imbalance in the microgrid, thereby enhancing the system stability. This is estab-lished through extensive simulation studies using PSCAD
    corecore